    來源:電工電氣發(fā)布時間:2017-11-17 08:17 瀏覽次數(shù):11
    1 036 MW機(jī)組高備變零序電壓U0偏高的分析及處理
     
    楊彪,曾向榮,李洪
    (華能海門電廠,廣東 汕頭 515132)
     
        摘 要:高備變是保證電廠發(fā)電機(jī)組安全運行的基礎(chǔ)。針對華能海門電廠110 kV高備變在正常運行中零序電壓異常升高情況,分析了其對系統(tǒng)的影響,討論了引發(fā)異常的可能原因,經(jīng)多方面論證并針對性排查,確定原因為高備變中性點引出線與接地電阻間腐蝕產(chǎn)生氧化鋁致使中性點接地破壞所造成的,通過采取相應(yīng)的處理及防范措施,保證了高備變恢復(fù)正常運行。
        關(guān)鍵詞:變壓器;平衡繞組;零序電壓;中性點接地
        中圖分類號:TM835     文獻(xiàn)標(biāo)識碼:B     文章編號:1007-3175(2017)11-0038-03
     
    Analysis and Treatment of High Zero Sequence Voltage U0 of High-Voltage Standby Transform in
    1 036 MW Generator Sets
     
    YANG Biao, ZENG Xiang-rong, LI Hong
    (Huaneng Power International, INC. Haimen Power Plant, Shantou 515132, China)
     
        Abstract: The high-voltage standby transformer is the basis to ensure the safe operation of generator sets in power plant. Aiming at the abnormal rise of zero sequence voltage during the normal operation of 110 kV high-voltage standby transformer in Huaneng Haimen power plant, this paper analyzed the influence on the system and discussed the possible, abnormal causes. After the demonstration and targeted investigation, it is found that the aluminium oxide formed because of the corrosion between the high-voltage standby transformer neutral point lead wire and the grounding resistance. The corresponding treatment and precautionary measures are adopted to ensure the high-voltage standby transformer get right operation.
        Key words: transformer; balanced winding; zero sequence voltage; neutral-point earthing
     
    參考文獻(xiàn)
    [1] 董景義,段玉柱,張賢國,等. 平衡繞組在變壓器中的作用及連接線方式淺述[J]. 電工文摘,2009,46(6):20-23.
    [2] 賀家李,李永麗,董新洲. 電力系統(tǒng)繼電保護(hù)原理[M]. 北京:中國電力出版社,2010.
    [3] 黃禾,錢國超,鄒德旭,等. 平衡繞組引起變壓器低壓側(cè)電壓不平衡分析[J]. 云南電力技術(shù),2014,42(S1):60-61.

     

    亚洲无码av成人在线,亚洲影院AV无码一区二区,亚洲无码第二页,成人无码AV网站在线观看不卡 (function(){ var bp = document.createElement('script'); var curProtocol = window.location.protocol.split(':')[0]; if (curProtocol === 'https') { bp.src = 'https://zz.bdstatic.com/linksubmit/push.js'; } else { bp.src = 'http://push.zhanzhang.baidu.com/push.js'; } var s = document.getElementsByTagName("script")[0]; s.parentNode.insertBefore(bp, s); })();