PT勵磁及傳變特性在信號注入法測量電容電流中的應(yīng)用
張利花,伍弘
(國網(wǎng)寧夏電力有限公司電力科學(xué)研究院,寧夏 銀川 750011)
摘 要:傳遞到電壓互感器(PT)一次側(cè)的實際電流值與額定值存在一定的誤差,導(dǎo)致計算出的電容電流誤差較大。以實驗室電磁式電壓互感器為研究對象,通過對PT勵磁特性的試驗研究及試驗數(shù)據(jù)的分析,證明在注入不同頻率的信號時,PT勵磁特性曲線的飽和特性并不相同,也說明注入不合適頻段的信號時,PT勵磁特性會影響信號注入法測量電容電流的準(zhǔn)確度。進(jìn)一步對PT傳變特性進(jìn)行試驗研究及試驗數(shù)據(jù)分析,設(shè)定了注入信號的合適頻率范圍,從而改進(jìn)了信號注入法測量電容電流的測量環(huán)節(jié)。
關(guān)鍵詞:信號注入法;電容電流;PT勵磁特性;PT傳變特性;頻率范圍
中圖分類號:TM451 文獻(xiàn)標(biāo)識碼:A 文章編號:1007-3175(2018)01-0046-05
Application of Excitation and Transmission Characteristic of Potential Transformer in Measurement of
Capacitive Current by Signal Injection Method
ZHANG Li-hua, WU Hong
(Power Research Institute of State Grid Ningxia Electric Power Company, Yinchuan 750011 , China)
Abstract: The actual current values delivered to the primary side of the potential transformer (PT) have some errors with the rated values, to result in greater errors in the calculated capacitive current. Taking the electromagnetic voltage transformer in laboratory for example, this paper analyzed the experimental study and test data of PT excitation characteristic to certify that the saturation characteristics of the excitation characteristic curves of the PT were different when signals with different frequencies injected. That’s why the excitation characteristic of PT had great influence on the accuracy in measurement of the capacitive current by signal injection method when the signal was injected into the inappropriate frequency band. Furthermore, the transmission characteristic test of PT was carried out and the test data were analyzed to determine the frequency range of the injected signal, so as to improve the measurement link of the signal injection method of measuring the capacitive current.
Key words: signal injection method; capacitive current; excitation characteristic of potential transformer; transmission characteristic of potential transformer; frequency range
參考文獻(xiàn)
[1] 劉力,孫結(jié)中. 一種測量配電網(wǎng)容性電流的新方法[J]. 電網(wǎng)技術(shù),2001,25(5):63-65.
[2] 程玉凱,杜文風(fēng). 基于雙信號法的配電網(wǎng)電容電流測量[J]. 電測與儀表,2012,49(5):21-24.
[3] 趙正軍,姜新宇. 信號注入法在配電網(wǎng)電容電流測量中的研究[J]. 廣東電力,2004,17(6):25-28.
[4] 李毅敏,蔡旭. 中壓電網(wǎng)對地電容檢測的注入信號源設(shè)計[J]. 繼電器,2007,35(9):45-51.
[5] 陳麗華.電磁式電壓互感器的原理及幾種測試方法[J]. 電力與能源,2010(27):36-40.
[6] 杜志葉,阮江軍,王偉剛. 鐵磁諧振仿真模型的改進(jìn)[J]. 繼電器,2004,32(8):26-29.
[7] 阮全榮,王亮,施圍. 一種計及損耗的變壓器非線性模型[J]. 西安交通大學(xué)學(xué)報,2006,40(10):115-119.
[8] 郭欣沅. 電能計量系統(tǒng)對動態(tài)信號傳變特性研究[D]. 北京:華北電力大學(xué),2014.
[9] 崔楊胡,虔生,黃允凱. 任意頻率正弦波條件下鐵磁材料損耗計算[J]. 微電機(jī),2007,40(8):1-3.
[10] 董張卓,李養(yǎng)俊,徐建軍,等. 用于鐵磁諧振過電壓計算的電壓互感器模型[J]. 電力學(xué)報,2012,27(5):463-468.
[11] 吳茂林,崔翔張,衛(wèi)東. 電壓互感器寬頻傳遞特性的時域測量方法[J]. 華北電力大學(xué)學(xué)報,2004,31(1):25-28.
[12] 宋曉燕,孫巖洲,宋紫嫣, 等. 基于零序PT二次側(cè)注入信號的配電網(wǎng)電容電流測量新方法[J]. 電力系統(tǒng)保護(hù)與控制,2014,25(5):134-138.