一種快速解環保護及合解環方案
王彥國,余群兵,金震
(南京南瑞繼保電氣有限公司, 江蘇 南京 211102)
摘 要:線路合環運行時,當相鄰線路發生故障,且保護或開關拒動后,存在主變誤跳、擴大失電范圍風險。對合環線路對繼電保護的影響進行了分析,針對目前方案帶來的級差配合困難、設計回路改動量大、降低保護可靠性等問題提出了一種快速解環保護,避免失電范圍擴大,并對某些配網的合環轉電操作,提出了一種備自投方案,實現合解環程序化操作,在倒閘失敗后自動進行反向合解環,確保重要負荷不失電。
關鍵詞:合環線路;解環;繼電保護
中圖分類號:TM773 文獻標識碼:A 文章編號:1007-3175(2018)05-0046-05
A Kind of Fast Unlink Protection and Loop Closing Scheme
WANG Yan-guo, YU Qun-bing, JIN Zhen
(Nari-Relays Electric Co., Ltd, Nanjing 2111 02, China)
Abstract: When the line operating in loop closing mode and the adjacent lines happened to break down, the protection or switch refused to work, so that there were the main transformer breaking by mistake and the power loss range-enlarged risk. This paper analyzed the loop closing line impacts on the relay protection. Aiming at the difficulty of stage difference coordination caused by the existing scheme, the greatly changed design loop and the reduced protection reliability etc problems. This paper proposed a kind of fast unlink protection to avoid the power loss range-enlarged risk. A kind of spare power automatic switching scheme was proposed for the loop closing turning electricity operation of some distribution networks to realize the operation of loop closing line routinization operation. After the back brake broke down, the reverse loop closing started atomically to ensure the important load without losing power.
Key words: loop closing line; unlink; relay protection
參考文獻
[1] 張勇,姚建光,俞曉榮,等.具備快速合解環功能的備自投分析[J]. 江蘇電機工程,2012,31(1):61-63.
[2] 苑捷. 北京城區配電網合環分析[D]. 北京:華北電力大學,2007.
[3] 張紅霞,閆琴,何勇毅,等. 雙回線并列運行方式的利弊探討[J]. 寧夏電力,2009(S1):22-25.
[4] 吳玲,劉勤. 雙回線并列運行方式探討[J]. 四川電力技術,2014,37(1):59-62.
[5] 楊志棟,劉一,張建華,等. 北京10 kV配網合環試驗與分析[J]. 中國電力,2006,39(3):66-69.
[6] DL/T 584—2007 3 ~ 110 kV電網繼電保護裝置運行整定規程[S].
[7] GB/T 14285—2006 繼電保護和安全自動裝置技術規程[S].
[8] DL/T 684—1999 大型發電機變壓器繼電保護整定計算原則[S].
[9] 朱景富. 雙回線并列運行方式對系統及保護定值的要求[J]. 繼電器,2007,35(10):64-65.