中壓開關柜的二次優化設計
劉丙剛
天水長城開關廠有限公司,甘肅 天水 741018
摘 要:針對開關柜的二次設計存在斷路器的跳位監視回路沒有監視斷路器合閘回路的整體完好性、大電流開關柜的風機控制回路無法實現智能化控制等缺陷,分析了當前二次回路的設計方式,并通過與綜合保護裝置、繼電器配合試驗后,提出二次回路設計的優化方案,提高了開關柜運行的可靠性及智能化。
關鍵詞:中壓開關柜;合閘回路;跳位監視;風機控制回路;二次優化設計
中圖分類號:TM591 文獻標識碼:A 文章編號:1007-3175(2016)02-0023-03
Secondary Optimization Design of Medium Voltage Switchgear
LIU Bing-gang
Tianshui Changcheng Switchgear Co., Ltd, Tianshui 741018, China
Abstract: In allusion to the problems that in secondary design of switchgear, the skip monitoring circuit has non overall integrity of monitoring circuit breaker closing circuit and the draught fan control circuit of large current switchgear couldn’t realize intelligent control, this paper analyzed the design methods of secondary circuit. After coordinating test of comprehensive protector and relay, this paper proposed the optimization scheme of secondary circuit design, which raises the reliability and intelligence of switchgear operation.
Key words: medium voltage switchgear; closing circuit; skip monitoring; draught fan control circuit; secondary optimization design