高壓開關(guān)操作引起瞬態(tài)電磁干擾的實(shí)測分析
錢佳斌,王立輝,魏廣進(jìn)
東南大學(xué) 儀器科學(xué)與工程學(xué)院,江蘇 南京 210096
摘 要:為研究高壓開關(guān)重?fù)舸┻^程的發(fā)生規(guī)律,分析隔離開關(guān)和斷路器操作產(chǎn)生電磁騷擾的特性,對500kV變電站開關(guān)操作過程中導(dǎo)致二次回路的電磁干擾進(jìn)行現(xiàn)場測量,并對開關(guān)操作產(chǎn)生的騷擾電壓進(jìn)行時(shí)域和頻域特性分析,確定騷擾等級及主頻范圍。測量結(jié)果表明,就地匯控柜內(nèi)二次設(shè)備端口騷擾電壓幅值達(dá)到320V,頻率分布集中在45.83MHz之內(nèi)。斷路器操作時(shí)端口騷擾電壓有較大的幅值水平,尤其是斷路器分閘-合閘-分閘操作時(shí)端口騷擾電壓在幅值、微脈沖持續(xù)時(shí)間和上升沿上,相對于隔離開關(guān)操作有更為嚴(yán)重的情況出現(xiàn)。
關(guān)鍵詞:高壓開關(guān)操作;電磁騷擾;時(shí)頻特性;端口騷擾電壓
中圖分類號:TM561;TM564.1 文獻(xiàn)標(biāo)識碼:A 文章編號:1007-3175(2015)10-0046-05
Actual Measurement Analysis of Transient Electromagnetic Interference Caused by High-Voltage Switch Operation
QIAN Jia-bin, WANG Li-hui, WEI Guang-jin
School of Instrument Science and Engineering, Southeast University, Nanjing 210096, China
Abstract: In order to research the outbreak regularity of the repeated break down process, analysis was made to the characteristics of the electromagnetic disturbance caused by the isolation switch and circuit breaker operation. The electromagnetic disturbance of secondary circuits caused by the switching operation was measured in the field, when 500kV substation just put into operation. This paper analyzed the time and frequency characteristics of disturbance voltage in the transient process and determined the disturbance level and the range of dominant frequency. Measurement results show that the maximum disturbance voltage on the ports of secondary equipment in control cabinets is 320V, and the disturbance frequency is focus on the range of 45.83MHz. There is considerable disturbance voltage amplitude during circuit breaker closing operations. Especially, there is more serious situation on the amplitude, micro-pulse duration and rising time of the disturbance voltage during circuit breaker under opening-closing-opening operations.
Key words: high-voltage switch operation; electromagnetic interference; time-frequency characteristic; port disturbance voltage
參考文獻(xiàn)
[1] De Abreu Silveira C, Da Costa C A, Da Costa e Silva R, et al.Electromagnetic Environment Measurement under Steady-State Conditions in Utility Substations[C]//Transmission & Distribution Conference and Exposition,2006.
[2] 杜林,唐啟堯,陳輝.三峽電站GIS快速暫態(tài)過電壓現(xiàn)場試驗(yàn)及分析[J].高電壓技術(shù),2009,35(7):1743-1747.
[3] 張衛(wèi)東,陳沛龍,陳維江,等.特高壓GIS變電站VFTO對二次電纜騷擾電壓的實(shí)測與仿真[J].中國電機(jī)工程學(xué)報(bào),2013,33(16):187-196.
[4] 李志兵,陳維江,王浩,等.特高壓交流試驗(yàn)示范工程GIS隔離開關(guān)帶電操作試驗(yàn)[J].高電壓技術(shù),2012,38(6):1436-1444.
[5] 盧斌先,王澤忠,李成榕,等.500kV變電站開關(guān)操作瞬態(tài)電場測量與研究[J].中國電機(jī)工程學(xué)報(bào),2004,24(4):133-138.
[6] 李小建,鐘堯,王任,等.超高壓系統(tǒng)隔離開關(guān)操作電磁騷擾的時(shí)頻特性[J].高電壓技術(shù),2012,38(11):2889-2897.
[7] 張禹芳,宋繼明.500kV交流輸變電工程啟動調(diào)試中斷路器分合分試驗(yàn)的探討[J].電網(wǎng)技術(shù),2007,31(17):7-10.