110 kV GIS接地排和氣管溫升異常原因分析及處理
鐘智攀,史利龍,劉波
(上海思源高壓開關有限公司,上海 201108)
摘 要:介紹了一起110 kV氣體絕緣封閉開關設備(GIS)母線接地排和氣體管路溫升異常的分析處理過程。分析了紅外測溫、螺栓力矩檢測、電流檢測等結果,認為接地排面積不足和氣管未絕緣隔斷是導致溫升異常的主要原因。給出了增加相間接地排及氣管增加絕緣墊等整改措施,測試結果表明,整改后接地排和氣管溫升滿足標準和使用要求。
關鍵詞:氣體絕緣封閉開關設備;接地排;氣體管路;紅外測溫;溫升異常
中圖分類號:TM595 文獻標識碼:B 文章編號:1007-3175(2019)04-0039-03
Analysis and Treatment of Abnormal Causes of Grounding Row and Gas Pipe Temperature Rise in 110 kV GIS
ZHONG Zhi-pan, SHI Li-long, LIU Bo
(Shanghai Sieyuan High Voltage Switchgear Co.,Ltd, Shanghai 2011 08, China)
Abstract: This paper introduced the analysis and treatment process of 110 kV GIS bus grounding row and gas pipe abnormal temperature rise and analyzed the results of infrared temperature measurement, bolt moment detection and current detection. The main causes of abnormal temperature rise were the insufficient grounding row area and the uninsulated gas pipe partition. This paper gave some rectification measures including the increase of interphase grounding rows and gas pipe insulating mats. The testing results show that the rectified grounding row and gas pipe meet the operating requirements and the relevant standards.
Key words: GIS; grounding row; gas pipe; infrared temperature measurement; abnormal temperature rise
參考文獻
[1] 中國電力企業(yè)聯合會. 帶電設備紅外測溫診斷應用規(guī)范:DL/T 664—2008[S]. 北京:中國電力出版社,2008:6-7.
[2] 張國光. 電氣設備帶電檢測技術及故障分析[M]. 北京:中國電力出版社,2015.
[3] 國家電網公司運維檢修部. 電網設備帶電檢測技術[M]. 北京:中國電力出版社,2015.
[4] 中國電力企業(yè)聯合會. 輸變電設備狀態(tài)檢修試驗規(guī)程:DL/T 393—2010[S]. 北京:中國電力出版社,2010:20-21.
[5] 朱建軍, 王赟中, 崔紹平, 等. 紅外技術診斷高壓電氣設備內部缺陷[J]. 高電壓技術,2004,30(7):34-36.
[6] 國家電網公司生產技術部. 電網設備狀態(tài)檢測技術應用典型案例[M]. 北京:中國電力出版社,2014.
[7] 邵進,胡武炎,賈風鳴,等. 紅外熱成像技術在電力設備狀態(tài)檢修中的應用[J]. 高壓電器,2013,49(1):126-129.
[8] 黎斌.SF6 高壓電器設計[M]. 北京:機械工業(yè)出版社,2010.
[9] 陳寶怡. 紅外診斷技術在高壓斷路器內部發(fā)熱故障中的應用[J]. 高壓電器,2011,47(5):92-95.
[10] 中國電器工業(yè)協會. 高壓開關設備和控制設備標準的共用技術要求:GB/T 11022—2011[S]. 北京:中國標準出版社,2011:22-23.