550 kV GIS用三工位隔離開關(guān)開合母線轉(zhuǎn)換電流研究
朱傳運(yùn),黃坤鵬,薛紅濤,黃鑫,李偉強(qiáng)
(河南平高電氣股份有限公司,河南 平頂山 467001)
摘 要:開發(fā)了550 kV GIS用三工位隔離開關(guān),通過對(duì)開斷過程中絕緣配合設(shè)計(jì),預(yù)判放電通道,保證電弧僅在抗燒蝕能力強(qiáng)的動(dòng)、靜弧觸頭之間燃燒。型式試驗(yàn)后樣機(jī)的燒蝕工況分析表明,通過提高隔離開關(guān)分合閘速度,避免了開合過程中出現(xiàn)的電弧漂移現(xiàn)象,通過對(duì)電弧燃燒時(shí)間長(zhǎng)短及分散性統(tǒng)計(jì),合理解釋了分、合閘速度對(duì)電弧漂移的影響,驗(yàn)證了所設(shè)計(jì)的三工位隔離開關(guān)的合理性。
關(guān)鍵詞:隔離開關(guān);母線轉(zhuǎn)換電流;絕緣設(shè)計(jì)
中圖分類號(hào):TM564.1 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2019)06-0021-03
Research on Bus-Transfer Current of Three-Working-Position Disconnector Equiped in 550 kV GIS
ZHU Chuan-yun, HUANG Kun-peng, XUE Hong-tao, HUANG Xin, LI Wei-qiang
(Henan Pinggao Electric Co., Ltd, Pingdingshan 467001, China)
Abstract: The three-working-position disconnector equipped in 550 kV GIS was developed. The discharge path could be predicated by the insulation coordination design in the breaking course, to ensure that the arc only burnt between the moving and fixed contact with high erosion resistance ability. The ablation working condition of prototype after type test shows that the arc shift phenomenon could be avoided in the breaking and making course by improving the speed of disconnector’s breaking and making, and the impacts of its speed on the arc shift was explained reasonably by the statistics of arcing time length and its dispersibility, which verifies the rationality of the designed three-working-position disconnector.
Key words: disconnector; bus-transfer current; insulation design
參考文獻(xiàn)
[1] 賈志杰,甘德剛,李晶.±500 kV氣體絕緣金屬封閉輸電線路絕緣尺寸設(shè)計(jì)[J]. 電網(wǎng)技術(shù),2011,35(8):192-196.
[2] 施衛(wèi)華, 阮寧暉, 王進(jìn). 高壓開關(guān)電器的發(fā)展及應(yīng)用[J]. 昆明冶金高等專科學(xué)校學(xué)報(bào),2005,21(5):45-51.
[3] 范廣偉,樊楚夫,黃實(shí),等. 氣體絕緣隔離開關(guān)開合母線轉(zhuǎn)換電流試驗(yàn)的分析[J]. 高壓電器,2017,53(4):215-219.
[4] 裴峰,蔡藝云. 隔離開關(guān)開合母線電流轉(zhuǎn)換能力分析[J]. 機(jī)電工程技術(shù),2015,44(9):134-137.