    1 100 kV GIL產(chǎn)品現(xiàn)場(chǎng)試驗(yàn)研究

    來(lái)源:電工電氣發(fā)布時(shí)間:2020-09-17 13:17 瀏覽次數(shù):811
    1 100 kV GIL產(chǎn)品現(xiàn)場(chǎng)試驗(yàn)研究
     
    孫瓊,許羅生,包聯(lián)霜
    (平高集團(tuán)有限公司,河南 平頂山 467001)
     
    摘 要:1 100 kV 氣體絕緣金屬封閉輸電線路(GIL) 設(shè)備為世界范圍內(nèi)較先應(yīng)用,目前尚無(wú)完善的現(xiàn)場(chǎng)交接試驗(yàn)方案,為解決這一現(xiàn)狀,對(duì)制約1 100 kV GIL 現(xiàn)場(chǎng)交接試驗(yàn)的項(xiàng)目進(jìn)行了分析研究。通過(guò)創(chuàng)新現(xiàn)場(chǎng)主電阻和氣體密度測(cè)量方法,將常規(guī)電阻測(cè)試中的正極或負(fù)極電流測(cè)試線用1 100 kV GIL 外殼代替,并設(shè)計(jì)專門的電阻測(cè)量結(jié)構(gòu),解決了現(xiàn)場(chǎng)測(cè)試線長(zhǎng)度不足的難題;通過(guò)制作專門的硬質(zhì)檢漏工裝,解決了現(xiàn)場(chǎng)檢漏氣體定量不準(zhǔn)確的問(wèn)題。該方案的實(shí)施,解決了困擾1 100 kV GIL 現(xiàn)場(chǎng)交接試驗(yàn)的困難。
    關(guān)鍵詞:氣體絕緣金屬封閉輸電線路(GIL);試驗(yàn)方案;現(xiàn)場(chǎng)試驗(yàn);管廊
    中圖分類號(hào):TM75 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2020)09-0043-04
     
    Study on Field Test of 1 100 kV GIL Product
     
    SUN Qiong, XU Luo-sheng, BAO Lian-shuang
    (Pinggao Group Co., Ltd, Pingdingshan 467001,China)
     
        Abstract: The 1 100 kV GIL is the first application in the world. At present, there is no perfect on-site handover test scheme.In order to solve the problem, the project that restricts the 1 100 kV GIL field handover test was analyzed and researched.By innovating on-site main resistance and gas density measurement methods, replacing the positive or negative current test line in the conventional resistance test with a 1 100 kV GIL shell, and designing a special resistance measurement structure to solve the problem of insufficient field test line length.The problem of inaccurate gas quantification for on-site leak detection is solved though making special hard leak detection tooling.The implementation of this program solved the difficulties that plagued the 1 100 kV GIL field handover test.
        Key words: GIL; test scheme; field test; pipe corridor
     
    參考文獻(xiàn)
    [1] 劉振亞. 中國(guó)電力與能源[M]. 北京:中國(guó)電力出版社,2012.
    [2] 王浩. 特高壓變電站用GIL關(guān)鍵技術(shù)研究[R]. 北京:中國(guó)電力科學(xué)研究院,2017.
    [3] 阮全榮,謝小平. 氣體絕緣金屬封閉輸電線路工程設(shè)計(jì)研究與實(shí)踐[M]. 北京:中國(guó)水利水電出版社,2011.
     

     

    亚洲无码av成人在线,亚洲影院AV无码一区二区,亚洲无码第二页,成人无码AV网站在线观看不卡 (function(){ var bp = document.createElement('script'); var curProtocol = window.location.protocol.split(':')[0]; if (curProtocol === 'https') { bp.src = 'https://zz.bdstatic.com/linksubmit/push.js'; } else { bp.src = 'http://push.zhanzhang.baidu.com/push.js'; } var s = document.getElementsByTagName("script")[0]; s.parentNode.insertBefore(bp, s); })();