220 kV同塔雙回線路終端塔避雷器試驗分析
王少華,申劍,李特,周象賢,韓睿
(國網浙江省電力有限公司電力科學研究院,浙江 杭州 310014)
摘 要:電網中線路避雷器故障屢有發生,直接影響線路安全運行。對某220 kV 同塔雙回線路終端塔避雷器進行了測試及解體分析。試驗結果表明,避雷器直流1mA參考電壓。密封性能符合標準要求,局部放電測試未發現明顯放電信號,解體后避雷器內部未發現異常放電痕跡,判斷Ⅰ回線路避雷器爆炸為避雷器個別性內部缺陷造成,Ⅱ回線路故障放電并非避雷器引起。對線路進站避雷器安裝于終端塔上的選型進行了討論,建議相應避雷器應采用短間隙避雷器。
關鍵詞:避雷器;終端塔;密封性;間隙
中圖分類號:TM862 文獻標識碼:A 文章編號:1007-3175(2021)01-0051-03
Test Analysis of Line Arresters Installed on Terminal Tower of 220 kV
Double-Circuit Transmission Line on the Same Tower
WANG Shao-hua, SHEN Jian, LI Te, ZHOU Xiang-xian, HAN Rui
(State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China)
Abstract: Line arrester failures frequently occur in the power grid, it directly affecting the safe operation of the line. The lightning arresterfor the terminal tower of a 220kV double-circuit line on the same tower was tested and disassembled. The test results show that the 1 mADC reference voltage and sealing performance of the arrester meet the requirements of the standard. No obvious discharge signal is found inthe partial discharge test. No abnormal discharge traces are found inside the arrester after disassembly. It is judged that the explosion of thearrester in the I circuit is caused by individual internal defects, and II circuit fault discharge is not caused by the arrester. The selection of thelightning arrester installed on the terminal tower of the line inbound is studied, and it is suggested that the corresponding arrester should be ashort-gap arrester.
Key words: arrester; terminal tower; tightness; gap
參考文獻
[1] 許坤,周建華,茹秋實,等. 變壓器油中溶解氣體在線監測技術發展與展望[J] . 高電壓技術,2005,31(8):30-32.
[2] 王瀾蓉. 南京地區油色譜檢測技術的應用與研究[D]. 南京:東南大學,2016.
[3] 魯統賀. 變壓器油色譜在線監測及故障診斷技術的應用[D]. 濟南:山東大學,2017.
[4] 鄭一鳴,孫淑蓮,孫翔,等. 基于自適應小波分析的在線油色譜數據預處理方法[J] . 浙江電力,2016,35(11):1-6.
[5] 薛朋駿. VxWorks系統的文件訪問控制技術研究[D]. 鎮江:江蘇科技大學,2016.
[6] 李鵬. 電力變壓器油相色譜在線監測技術的應用研究[D]. 保定:華北電力大學,2015.