750 kV并聯(lián)電抗器油色譜異常故障診斷及分析
王永奇,王懷祥,李明,周家戌,常永哲
(國網(wǎng)甘肅省電力公司電力科學(xué)研究院,甘肅 蘭州 730050)
摘 要: 介紹了一起750 kV 并聯(lián)電抗器出現(xiàn)油色譜監(jiān)測數(shù)據(jù)嚴(yán)重異常的故障,分析了故障產(chǎn)生的原因,利用特征氣體、大衛(wèi)三角和改良“三比值”等油色譜分析手段,結(jié)合診斷性電氣試驗(yàn),成功診斷出了該電抗器故障是屬于放電性故障,經(jīng)過吊罩檢查分析,電抗器內(nèi)部放電是由于地腳螺栓松動(dòng)引起的,給出了應(yīng)對(duì)措施,為故障處理提供了方案。
關(guān)鍵詞: 電抗器;油色譜分析;故障診斷;處理
中圖分類號(hào):TM471+.2 文獻(xiàn)標(biāo)識(shí)碼:B 文章編號(hào):1007-3175(2015)03-0052-03
Fault Diagnosis and Analysis of Abnormal Oil Chromatographic of 750 kV Shunt Reactors
WANG Yong-qi, WANG Huai-xiang, LI Ming, ZHOU Jia-xu, CHANG Yong-zhe
(Electric Power Research Institute of Gansu Electric Power Corporation, Lanzhou 730050, China)
Abstract: Introduction was made to the abnormal oil chromatographic monitoring data fault that happened to 750 kV shunt reactors. This paper analyzed the reasons of the faults, took oil chromatographic analysis methods, such as characteristic gas, Duval’s triangle and improved three-ratio and combined with diagnostic electrical test, to successfully diagnose that the reactor fault belonged to discharging fault. By making inspection and analysis to the hoisting cover, prevention measures have been made to avoid the inner discharge of reactors caused by the looseness of anchor bolts, which provides the solution for faults treatment.
Key words: reactor; analysis of oil chromatographic; malfunction diagnosis; treatment
參考文獻(xiàn)
[1] 李德志,曹宏偉,朱華,等.電力變壓器油色譜分析及故障診斷技術(shù)[M].北京:中國電力出版社,2013.
[2] 田成鳳.一臺(tái)220 kV變壓器油色譜異常的分析與處理[J].天津電力技術(shù),2009(2):27-31.
[3] 耿基明,郭曉峰.應(yīng)用變壓器油色譜分析判斷變壓器故障[J].變壓器,2006,46(11):44-46.
[4] 王楠,王軍亮.110 kV變壓器油色譜異常故障的分析[J].電力安全技術(shù),2014,16(5):40-43.