互感器二次回路施工驗收常見問題分析及防范
史文玎,楊奇
(山西潞光發電有限公司,山西 長治 046600)
摘 要:對某火電廠施工調試期間發生電壓互感器一次設備布置差異導致相序相反、一次電壓與二次電壓相位相反,及電流互感器不同準確級的二次繞組使用錯誤,不同零序電流互感器對應負荷接線錯誤等問題,提出了比對設備出廠圖紙與設計院圖紙差異,規范二次回路接線,設備帶電后進行電壓與電流暫態、穩態幅值相位檢查,對比直流電阻值及伏安特性參數等施工注意事項及驗收的方法,有效確保了回路接線的正確性。
關鍵詞: 互感器;二次繞組;布置順序;直流電阻
中圖分類號:TM45 文獻標識碼:B 文章編號:1007-3175(2024)01-0038-04
Analysis and Prevention of Common Problems in Construction and
Acceptance of Secondary Circuit of Mutual Inductor
SHI Wen-ding, YANG Qi
(Shanxi Luguang Power Generation Co., Ltd, Changzhi 046600, China)
Abstract: This paper is based on the difference in the layout of the primary equipment of the voltage mutual inductor during the construction and commissioning of a thermal power plant, which leads to the opposite phase sequence, the opposite phase of the primary voltage and the secondary voltage, the wrong use of the secondary winding of the current mutual inductor with different accuracy levels, and the wrong wiring of the corresponding load of different zero-sequence current mutual inductors. The method of comparing the difference between the factory drawing and the design institute drawing, standardizating the secondary circuit wiring, checking the voltage and current transient and steady-state amplitude phase after the equipment is charged, comparing the DC resistance value and voltammeter characteristic parameters and other construction considerations and acceptance are put forward, which effectively ensures the correctness of the circuit wiring.
Key words: mutual inductor; secondary winding; arrangement order; DC resistance
參考文獻
[1] 余云光,何磊,余煒. 電壓互感器錯誤接線分析與防范措施探索[J] . 云南電力技術,2019,47(5) :81-85.
[2] 楊奇. 一起發電機定子接地保護誤發信號的案例分析[J]. 電工電氣,2022(5) :74-76.
[3] 楊杰,徐智,鄭慶榮. 電流互感器二次回路相關故障及應對措施探究[C]//中國水力發電工程學會自動化專委會 2021 年年會暨全國水電廠智能化應用學術交流會論文集,2021.
[4] 張敏,宋艷偉,曾群文. 電流互感器二次回路檢修方法探究[C]//2022 年電力行業技術監督工作交流會暨專業技術論壇論文集,2022.
[5] 中國電力企業聯合會標準化管理中心. 繼電保護和電網安全自動裝置檢驗規程:DL/T 995—2016[S]. 北京:中國電力出版社,2018:4.