基于Matlab仿真的閃變儀自校驗及誤差校正研究
高燕1,吳陽2
1 東南大學 電氣工程學院,江蘇 南京 210096; 2 沭陽縣供電公司,江蘇 沭陽 223600
摘 要:為提高閃變儀的測量精度,在介紹IEC閃變儀的測量原理及短時閃變嚴重度計算方法的基礎上,論述了閃變儀的數字化實現模型及PID自校驗控制算法的實現,并采用統計排序法計算短時閃變嚴重度。針對不同波動頻率下短時閃變嚴重度的測量誤差引入多項式擬合校正,Matlab仿真結果表明,引入多項式擬合校正方法明顯提高了閃變儀的檢測精度。
關鍵詞:閃變;短時閃變嚴重度;自校驗;誤差校正
中圖分類號:TM933 文獻標識碼:A 文章編號:1007-3175(2013)02-0035-05
Research on Self Checking and Error Correction of Flicker Meter Based on Matlab Simulation
GAO Yan1, WU Yang2
1 School of Electric Engineering, Southeast University, Nanjing 210096, China;
2 Shuyang Power Supply Corporation, Shuyang 223600, China
Abstract:In order to improve the measurement precision of the flicker meter, on the basis of the IEC flicker meter measurement principle and the calculation methods of the short-term flicker severity, this paper discussed the model of digital flicker meter and the PID self-checking control algorithm, at the same time, the short-term flicker severity was calculated with statistic sequence. In allusion to the measurement error of the short-term flicker severity in different fluctuation frequency, polynomial fitting correction method was introduced and verified by the Matlab simulation experiment.
Key words: flicker; short-term flicker severity; self checking; error correction
參考文獻
[1] 肖湘寧,韓民曉,徐永海.電能質量分析與控制[M].北京:中國電力出版社,2010.
[2] IEC61000-4-15:2003 Flickermeter-Functional and Design Specifications[S].
[3] 王維慶,王海云,陳宇中.基于Matlab短時閃變嚴重度計算方法研究[J].新疆大學學報:自然科學版,2007,24(3):282-285.
[4] 趙剛,施圍,林海雪.閃變值計算方法的研究[J].電網技術,2001,25(11):15-18.
[5] 高彥靜.電壓波動的檢測方法和閃變計算研究[D].天津:天津大學,2010.
[6] 馬玉龍,劉連光,張建華,等.IEC閃變測量原理的數字化實現方法[J].中國電機工程學報,2001,21(11):93-96.
[7] 吳煒,陳勁操.基于Matlab的數字式IEC閃變儀分析研究[J].電測與儀表,2009,46(4): 50-52.
[8] 趙海翔,陳默子,戴慧珠.閃變值離散化計算的誤差分析及其應用[J].電網技術,2004,28(13):84-87.
[9] 劉大貴,王維慶,王海云.基于IEC閃變儀測試系統的仿真研究[J].自動化儀表,2011,32(4):59-61.
[10]Wicznski Grzegorz.Analysis of Voltage Fluctuations in Power Networks[J].IEEE Transactions on Instrumentation and Measurement, 2008, 57(11):2655-2664.