一臺220 kV變壓器總烴超標分析及處理
趙全勝,邵慶華,宋建輝,左魁生,劉新海
鄭州供電公司,河南 鄭州 450006
摘 要: 通過對變壓器油定期化驗分析,提前發(fā)現(xiàn)變壓器內(nèi)部故障,判斷故障原因并及時處理故障, 避免了一次重大設(shè)備損壞事故。油色譜分析作為變壓器故障分析的一種手段非常有效,但還應(yīng)綜合考慮其他試驗結(jié)果及現(xiàn)場具體情況。在變壓器的運行維護中,應(yīng)定期對其附屬設(shè)備進行檢查,避免設(shè)備超期服役造成的故障。1# 主變大修后各項指標沒有明顯增長,保證了變壓器的安全穩(wěn)定運行。
關(guān)鍵詞: 變壓器油;油色譜分析;烴超標
中圖分類號:TM407 文獻標識碼:B 文章編號:1007-3175(2013)03-0034-03
Analysis and Treatment of Total Hydrocarbon Overweight in a 220 kV Main Transformer
ZHAO Quan-sheng, SHAO Qing-hua, SONG Jian-hui, ZUO Kui-Sheng, LIU Xin-hai
Zhengzhou Electric Power Company, Zhengzhou 450006, China
Abstract: Periodical assay and analysis of transformer oil made interior fault of transformers detected in advance, fault causes judged and fault processed in time, which avoided a great damage to equipment. Oil chromatographic analysis was a kind of good way of transformers fault analysis, but the other testing result and onsite conditions should still be considered comprehensively. During the maintenance of transformers operation, periodical inspections were carried out for the transformers accessory equipment to avoid fault due to extended activity duty of equipment. After the number one main transformer was overhauled, each index of the transformer had no obvious increase, which ensures safe and stable operation of the transformer.
Key words: transformer oil; oil chromatographic analysis; hydrocarbon overweight
參考文獻
[1] DL/T 572-2010 電力變壓器運行規(guī)程[S].
[2] GB/T 6451-2008 油浸式電力變壓器技術(shù)參數(shù)和要求[S].
[3] GB/T 7252-2001 變壓器油中溶解氣體分析和判斷導則[S].
[4] 曹敦奎.變壓器油中氣體分析診斷與故障檢查[M].北京:中國電力出版社,2005.