故障電流限制器頻繁永久閉鎖合閘的原因分析及改進(jìn)
于軍1,吳金祥1,王少華2
1 浙江省電力公司檢修分公司,浙江 杭州 310009;
2 浙江省電力公司電力科學(xué)研究院,浙江 杭州 310014
摘 要: 介紹了華東500 kV 瓶窯變電所故障電流限制器在線路負(fù)荷電流正常增加過程中,頻繁出現(xiàn)的光通道閥損壞、主動旁路保護(hù)動作及永久閉鎖合閘情況,分析了導(dǎo)致故障電流限制器頻繁永久閉鎖合閘的根本原因,提出了修改閥控與監(jiān)測系統(tǒng)程序,增大閥高電位控制單元檢測時間,以及增加監(jiān)控后臺遠(yuǎn)方復(fù)歸功能的改進(jìn)方法,為變電站無人值班提供了技術(shù)支撐。
關(guān)鍵詞: 故障電流限制器;永久閉鎖;手動復(fù)歸;閥基電子設(shè)備;遠(yuǎn)方復(fù)歸
中圖分類號:TM506 文獻(xiàn)標(biāo)識碼:B 文章編號:1007-3175(2013)11-0029-03
Cause Analysis and Improvement of Frequently Permanent Close of Fault Current Limiter
YU Jun1, WU Jin-xiang1, WANG Shao-hua2
1 Maintenance Branch of Zhejiang Electric Power Corporation, Hangzhou 310009, China;
2 Electric Power Research Institute of Zhejiang Electric Power Corporation, Hangzhou 310014, China
Abstract: For the fault current limiter in 500 kV Pingyao substation, introduction was made to the phenomena such as optical channel valve damage, active bypass protection action and permanent closing in the normal increasing process of line load current. This paper analyzed fundamental causes making the fault current limiter frequently permanent closing; raised modifying valve control and monitoring system programs; increased test time of thyristor control unit and added to monitor the remote reset function, which provided technical support for unattended substation.
Key words: fault current limiter; permanent close; hand reset; valve-based electronic device; remote reset
參考文獻(xiàn)
[1] 金雪芬,戴朝波,武守遠(yuǎn),等.故障電流限制器對繼電保護(hù)的影響[J].電網(wǎng)技術(shù),2010,34(6):98-105.
[2] 謝煒,李欣,戴朝波.故障電流限制器的研究現(xiàn)狀及展望[J].大功率變流技術(shù),2011(4):17-21.
[3] 武守遠(yuǎn),荊平,戴朝波,等.故障電流限制技術(shù)及其新進(jìn)展[J].電網(wǎng)技術(shù),2008,32(24):23-32.
[4] 楊國慶,祝瑞金,余穎輝,等. 華東電網(wǎng)500 kV故障電流限制器應(yīng)用研究[J]. 華東電力,2008,36(11):23-25.
[5] 趙強(qiáng),張麗.故障電流限制器現(xiàn)狀及應(yīng)用前景[J].電力建設(shè),2008,29(1):44-47.
[6] 昃萌,廖敏.故障電流限制器的晶閘管閥觸發(fā)與監(jiān)測系統(tǒng)[J].電工技術(shù)學(xué)報,2010,10(25):191-195.