消弧線圈新型自動(dòng)調(diào)諧方式的研究
夏小飛
廣西電力科學(xué)研究院,廣西 南寧 530023
摘 要: 根據(jù)10 kV 配電網(wǎng)的實(shí)際情況,就隨調(diào)式消弧線圈對(duì)配電網(wǎng)安全運(yùn)行的影響進(jìn)行系統(tǒng)的仿真計(jì)算,評(píng)估其優(yōu)缺點(diǎn),并提出了一種消弧線圈的新型調(diào)諧方式:隨調(diào)式消弧線圈正常運(yùn)行時(shí)預(yù)置40% 脫諧度。仿真結(jié)果表明,該新型調(diào)諧方式解決了目前系統(tǒng)廣泛應(yīng)用的隨調(diào)式消弧線圈故障選線成功率低的問題,有利于配電網(wǎng)的安全可靠運(yùn)行。
關(guān)鍵詞: 消弧線圈;欠補(bǔ)償;間歇性電弧接地;接地選線;評(píng)估優(yōu)化
中圖分類號(hào):TM55 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2013)11-0015-05
Study on New Type of Automatic Tuning Method for Arc Suppressing Coil
XIA Xiao-fei
Guangxi Electric Power Research Institute, Nanning 530023, China
Abstract: According to actual situation of 10 kV distribution network, this paper carried out the system simulation calculation for the impact of post-set arc suppressing coil on safety operation of distribution network and evaluated its advantages and disadvantages.This paper raised a new type of tuning method of arc suppressing coil. 40% detuning degree was preset in normal operation of postset arc suppressing coil. Simulation result shows that the new type of tuning method has solved the low successful rate problem of existing system widely applied in post-set arc suppression coil fault line selection, which is favorable for safety and reliable operation of distribution network.
Key words: arc suppressing coil; under compensation; intermittent arc grounding; grounding line selection; evaluation and optimization
參考文獻(xiàn)
[1] DL/T 620-1997 交流電氣裝置的過電壓保護(hù)和絕緣配合[S].
[2] 韓愛芝,曾定文,魯鐵成. 配電網(wǎng)間歇性電弧接地過電壓的仿真分析與對(duì)策[J]. 高壓電器,2010,46(1):72-75.
[3] 陳恒.不同消弧線圈性能分析與試驗(yàn)驗(yàn)證[D].上海:上海交通大學(xué),2010.
[4] 王鵬,顧萌.預(yù)調(diào)式和隨調(diào)式消弧線圈與鐵磁諧振分析[J].電工技術(shù),2011(1):71-73.
[5] 陸國慶,張瑞紅,劉味果,等.小擾動(dòng)法與并聯(lián)電阻法選線方式的比較分析[J].電力設(shè)備,2007,8(8):24-27.
[6] 陳國平.高阻接地系統(tǒng)的微機(jī)選線及故障定位裝置研制[D].長(zhǎng)沙:湖南大學(xué),2010.
[7] 孫福生.諧振接地系統(tǒng)小電流接地故障選線技術(shù)評(píng)價(jià)體系及分析[D].濟(jì)南:山東大學(xué),2010.
[8] 連鴻波,譚偉璞,裴善鵬,等. 諧振接地電網(wǎng)預(yù)隨調(diào)補(bǔ)償方式及其實(shí)現(xiàn)[J]. 電力系統(tǒng)自動(dòng)化,2005,29(21):83-88.
[9] 吳清,許云峰.小電流接地選線裝置的現(xiàn)場(chǎng)接地選線試驗(yàn)[J].電力系統(tǒng)自動(dòng)化,2006,30(17):105-107.