封閉母線絕緣子故障導致定子接地保護動作事故分析
薛麗麗,陳熙平,陳強,曹鋼,王文松
(錦屏水力發電廠,四川 西昌 615000)
摘 要:為了確定故障類型和故障地點,對故障錄波裝置采集的波形及數據進行了分析,根據分析結果進行檢查,檢查結果與分析結果一致。將故障錄波裝置波形及數據與RCS-985GW裝置自身的報告和波形進行對比,討論了保護中存在的問題并提出了相應的建議。
關鍵詞:定子接地保護;諧振;數據分析;母線絕緣子故障
中圖分類號:TM216 文獻標識碼:B 文章編號:1007-3175(2014)03-0037-04
Incident Analysis of Stator Grounding Protection Action Caused by Blocking Bus-Bar Insulator Fault
XUE Li-li, CHEN Xi-ping, CHEN Qiang, CAO Gang, WANG Wen-song
(Jinping Hydraulic Power Plant, Xichang 615000, China)
Abstract: In order to confirm the fault type and location, this paper anatomized the waveforms and data collected by the fault recording device and carried out inspection according to the analysis results. The inspecting results were consistent to the analysis results. The waveforms and data of the fault recording device were contrasted with the reports and waveforms from the device RCS985GW. The problems existed in protection were discussed and the corresponding suggestions were proposed.
Key words: stator grounding protection; resonance; data analysis; bus-bar insulator fault