雷電沖擊電壓下局部放電檢測方法有效性研究
鄢陽,張連星
(國網(wǎng)電力科學(xué)研究院武漢南瑞有限責(zé)任公司,湖北 武漢 430074)
摘 要:為了研究沖擊電壓下局部放電現(xiàn)象,搭建了沖擊電壓發(fā)生裝置。以油紙絕緣氣隙模型為試驗對象,通過超聲波法、高頻電流法和超高頻法對雷電沖擊電壓波形下的局部放電信號進行測量,列出典型波形進行對比分析。試驗結(jié)果表明,高頻電流法能有效提取局部放電脈沖,為進一步研究沖擊電壓下局部放電特征和機理提供參考。
關(guān)鍵詞:沖擊電壓;局部放電;高頻電流法;超聲波法;超高頻法
中圖分類號:TM866 文獻標(biāo)識碼:A 文章編號:1007-3175(2016)04-0046-03
Validation Study of Partial Discharge Detection Method Under Lightning Impulse Voltage
YAN Yang, ZHANG Lian-xing
(Wuhan Nari Limited Liability Company of State Grid Electric Power Research Institute, Wuhan 430074, China)
Abstract: In order to research the partial discharge (PD) phenomena under impulse voltage (IV), a device of IV has been set up. Taking the air gap of oil-paper insulation model as testing object, PD pulses signal under Lightning IV was detected by AE, HFCT and UHF. The typical waveforms were listed for analyzing. The testing results show that HFCT can effectively extract the PD pulses, which could play a very important role for further studying PD characteristic and mechanism under IV.
Key words: impulse voltage; partial discharge; HFCT; AE; UHF
參考文獻
[1] 唐志國,王彩雄,陳金祥,等.局部放電UHF脈沖干擾的排除與信號的聚類分析[J].高電壓技術(shù),2009,35(5):1026-1032.
[2] 杜伯學(xué),陸宇航,古亮.基于光學(xué)電流傳感器的局部放電檢測[J].電力系統(tǒng)自動化,2008,32(16):66-72.
[3] 孫才新,許高峰,唐炬,等.檢測GIS局部放電的內(nèi)置傳感器的模型及性能研究[J].中國電機工程學(xué)報,2004,24(8):89-93.
[4] 司文榮,李軍號,袁鵬,等.直流下油中局部放電脈沖波形測量與特性分析[J].西安交通大學(xué)學(xué)報,2008,42(4):284-287.
[5] 司文榮,李軍浩,袁鵬,等.直流電壓下油紙絕緣中局部放電的超高頻特性[J].高電壓技術(shù),2008,34(7):1136-1141.
[6] 楊眉,李劍,楊麗君,等.變壓器典型油紙絕緣局部放電特性[J].重慶大學(xué)學(xué)報,2007,30(2):46-49.
[7] 王國利,郝艷捧,賈志東,等.電力變壓器典型局放模型放電脈沖的特性研究[J].高電壓技術(shù),2001,27(2):5-8.
[8] 高文勝,王猛,談克雄,等.油紙絕緣中局部放電的典型波形及其頻譜特性[J].中國電機工程學(xué)報,2002,22(2):1-5.
[9] Hitoshi O.Recent progress and future perspective on condition monitoring and diagnostic techniques for power equipment in Japan[C]//Proceeding of International Conference on Condition Monitoring and Diagnosis,Beijing,2008.
[10] Hayakawa N,Yoshiake Y, Koshino N,et a1.Impulse partial discharge characteristics and their mechanisms under non-uniform electric field in N2/F6 Gas Mixtures[J].IEEE Transactions on Dielectrics and Electrical Insulation,2005,12(5):1035-1041.
[11] 孫振權(quán),趙學(xué)風(fēng),李繼勝,等.雷電沖擊電壓下油紙絕緣氣隙模型的局部放電測量與分析[J].西安交通大學(xué)學(xué)報,2009,43(12):75-80.
[12] 孫強,董明,任重,等.現(xiàn)場用GIS沖擊耐壓試驗及局部放電檢測裝置設(shè)計[J].高電壓技術(shù),2012,38(3):639-644.
[13] IEC 60060-3:2006 High voltage test techniques-Part3:Definitions and requirements for on-site tests[S].