1 100 kV斷路器切電容器組性能研究
郭自豪,盧鵬,付佳佳
(河南平高電氣股份有限公司,河南 平頂山 467001)
摘 要:從滅弧室開斷電場對某1 100 kV斷路器的切電容器組性能進行了分析,通過斷路器的真型試驗考察了1 100 kV斷路器在BC1 及BC2 級試驗時的開斷性能。理論分析結果表明1 100 kV斷路器具備滿足國標要求切電容器組性能,基于理論分析結果,并按照GB 1984試驗要求,完成了1 100 kV斷路器切電容器組所有試驗內容,驗證了該1 100 kV斷路器切電容器組的優(yōu)良性能。
關鍵詞:電場分析;1 100 kV 切電容器組;BC1 級;BC2 級
中圖分類號:TM561 文獻標識碼:B 文章編號:1007-3175(2017)07-0051-04
Research on Property of 1 100 kV Circuit Breaker Shunt Capacitor Bank
GUO Zi-hao, LU Peng, FU Jia-jia
(Henan Pinggao Electric Co., Ltd, Pingdingshan 467001, China)
Abstract: From making and breaking electric field of arc-extinguishing chamber, this paper analyzed certain 1 100 kV circuit breaker shunt capacitor bank property. The real model test inspected the 1 100 kV circuit breaker making and breaking property of BC1 and BC2 level tests.The theoretical analysis result slows that the 1 100 kV circuit breaker meets the requirements of shunt capacitor bank property. Based on the theoretical analysis result, according to the requirements of GB 1984 test, all test content were carried out for the 1 100 kV circuit breaker shunt capacitor bank, which verifies the good property of this 1 100 kV circuit breaker shunt capacitor bank.
Key words: electric field analysis; 1 100 kV shunt capacitor bank; BC1 level; BC2 level
參考文獻
[1] 林莘. 現(xiàn)代高壓電器技術[M].2 版. 北京:機械工業(yè)出版社,2011:35-51.
[2] 劉志遠,楊和. 真空開關的電容器組投切[C]//2012輸變電年會論文集,2012.
[3] 李凱宇,李勁彬.35 kV斷路器切電容器組引起三相短路故障的分析[J]. 電力電容器與無功補償,2014,35(1):83-89.
[4] 陳辰杰,鄭學賢.35 kV投切并聯(lián)電容器組的過電壓分析與抑制[J]. 大眾科技,2012(10):87-90.
[5] 段雄英,廖敏夫,丁富華,等. 基于真空斷路器的并聯(lián)電容器組相控投切裝置[J]. 電工技術學報,2007,22(10):78-84.